RDA-ENC6B

Radia Lighting 6-Space Enclosure with 6 Breakers

Description
120 VAC
Part #FG606-13

D-Tools Certified Product

This product can be found in the D-Tools manufacturer product database and specified as a third party device when building and proposing a system using D-Tools System Integrator software. D-Tools data includes attributes that make it easier to sell, design, and install systems including: overview, specifications, images, product documentation and more. AMX is a member of the D-Tools Manufacturer Vantage Point (MVP) program designed to provide D-Tools customers the most up-to-date product information.

COUNTRY OF ORIGIN: UNITED STATES

To satisfy the requirements/regulations of existing or future government programs, this two-letter code is being provided to designate the country of origin for this product.

(Click here for a list of all countries and their respective two-letter code.)

OVERVIEW
The RDA-ENC6B enclosure provide secure mounting for AMX Lighting and PROLink controllers, and lighting modules. The enclosure also contain 6 circuit breakers. This enclosure is CE, UL, and C-UL approved. It includes circuit breakers and terminals for multi-phase wiring. It also provides 18 knockouts for 1/2", 3/4", and 1" conduits.

FEATURES

  • Supports multi-phase wiring for one RDC-PDC Dimmer Card
  • Includes six 20A circuit breakers and terminals for multiphase wiring
  • Provides six spaces for Radia Lighting Modules
  • Mounts RDC-PDC card in dedicated, pre-wired compartment
  • 18 knockouts for 1/2", 3/4", and 1" conduit
  • Supports up to 18 dimming channels per unit (3 RE-DM6)

SPECIFICATIONS

DIMENSIONS (HWD)
24" x 18" x 6" (60.7 cm x 45.7 cm x 15.2 cm)

DIMENSIONS FROM CENTER LINES

  • A to B = 16.0" (40.6 cm)
  • B to C = 22.88" (58.1 cm)

WEIGHT
16.5 lbs (7.5 kg)

CONFIGURATIONS

  • ENC6B/120: 20 A Breakers
  • ENC6B/240: 10 A Breakers

LINE INPUTS

  • 140 A max per enclosure
  • Input 1 feeds channels 1, 4, 7, and 10
  • Input 2a feeds channels 5 and 11
  • Input 2b feeds channels 2 and 8
  • Input 3 feeds channels 3, 6, 9, and 12
  • Breakers are UL 489 listed 10,000 AIC, 100% Switching Duty, Hydraulic-Magnetic

WIRING

  • Maximum input wire #1/0 AWG (50mm²)
  • Maximum line input is 140 A (per enclosure )
  • Torque input wire to 44 in-lbs (5.0 N/m)
  • Wire stripping length: 0.67 inches (17 mm)